Planned Maintenance
Learning Center
More Questions

Question:
As a transmission owner, what should I do if I need to change a transmission outage ticket and it is locked?

Answer:
Contact the PJM eDART Change Hotline, Reliability Engineer (RE), or Power Dispatcher (PD). They will unlock the ticket.

Transmission Outage Ticket FAQs
  1. How do I see the transmission outages that are shown on OASIS, in eDART?
  2. How long does a completed transmission outage remain on the OASIS Transmission Facilities Outage List before it is removed from the listing?
  3. How do I see transmission outages that were previously displayed in the OASIS Transmission Facilities Outage List but have since been completed and removed from this list?
  4. As a transmission owner, must I submit a transmission outage ticket through eDART for trippings?
  5. As a transmission owner, when should I use the “Informational/Hotline Work” checkbox?
  6. As a transmission owner, what should I do if I need to change a transmission outage ticket and it is locked?
  7. As a transmission owner, when should I use the Emergency checkbox?
  8. How are transmission lines arranged in the eDART database?
  9. As a transmission owner, what should I do if I need to put in a ticket but cannot find a certain piece of equipment in eDART?
  10. As a transmission owner, where do I go to find notifications of other companies’ transmission outages?
  11. As a transmission owner, once I acknowledge a transmission outage notification, how can I see it again?
  12. As a transmission owner, what should I do when I receive notification of transmission outages that I don’t want to know about?
  13. As a transmission owner, how can I view all the equipment that I am supposed to receive outage notifications for?
  14. As a transmission equipment owner, which equipment requires eDART transmission outage tickets?
  15. When do I need to verbally notify PJM of transmission outages?
  16. When will I receive verbal notification from PJM about submitted Outage Tickets?
  17. As a transmission owner, can I see a report of generation outages in my transmission zone?
  18. As a transmission owner, how do I access reactive capability information for units in my transmission zone?
  19. As a transmission owner, how do I view the reactive tickets for my zone?
  20. How should I submit an eDART ticket for a job that starts at midnight?
  21. As a transmission owner, what should I put in the Description of Work field?
  22. As a transmission owner, how can I get NERC TADS data to be sent to NERC from eDART?