Question:
How does TERM set the default ratings and what are the rules for entering new ratings?

Answer:

Every piece of equipment that was newly added to the PJM network model has ratings of 0 MVA across the board.

When entering a new ticket manually, by default, TERM sets short-term emergency ratings to be equal to long-term emergency ratings. If needed, the user can manually enter values for the short-term emergency ratings that are different than long-term emergency ratings.

The following rules apply to all the TERM tickets:

  • For each temperature set, the following rule applies: normal ≤ long-term emergency ≤ short-term emergency ≤ load dump.
  • All manually entered load dump ratings must be at least three percent higher than their corresponding short term emergency ratings.
  • Night ratings are generally greater than day ratings, although there is no rule to this effect.
  • The ratings at a given temperature set are generally expected to be greater than or equal to the ratings at the temperature set above it.


TERM FAQs
  1. How does TERM set the default ratings and what are the rules for entering new ratings?
  2. When I submit a TERM ticket, is it automatically applied to the PJM EMS?
  3. What criteria does PJM use for approving TERM tickets?
  4. Is TERM training available?
  5. How do I update impedance and charging values?
  6. How can I upload rating values in bulk to TERM?
  7. What types of equipment need ratings? Are ratings required for all equipment?
  8. Where should ratings be applied for each type of equipment?
  9. How are tie line ratings coordinated by PJM?
  10. How can I submit flow breaker ratings?
  11. How do I contact TERM Support?
  12. How do I add email addresses to our transmission owner notification list from PJM?